Calculation method
- Operation: sum of quantities × unit operating watts.
- Simultaneous start-ups: sum of quantities × watts Unit start-up TOTALS.
- Staged start: total in operation + larger unit supplement (total start less operation). Only one unit starts, even if several units of an apparatus are planned.
- The continuous and peak targets each apply the chosen margin, then are rounded to the upper watt.
Illustrative example: A refrigerator and a freezer, each rated at 700 W running and 1,200 W total starting power, require 1,400 W running, 2,400 W if both start together, or 1,900 W if only one unit starts at a time. With a 20% margin in staggered mode, the targets are 1,680 W continuous and 2,280 W peak.
The list includes the old categories and their devices. Historical start-up zeros are presented as an absence of supplement in the illustrative scenario, thus a total start equal to the operation. The inconsistent data of the heat pump is left to be entered. Capacity labels and powers remain to be confirmed on each device.